Standon Model S96 Installation Guide

Measure Distance from flange to floor.
  1. Measure distance from bottom of flange to finish floor elevation. Inspect flange edge surface and remove any casting bumps or tab's.
Cut Sch. 40 pipe 4" shorter.
  1. Cut a piece of Sch. 40 steel pipe 4" less than the previously measured distance.
Thread collar onto stud of saddle and insert Sch. 40 pipe into collar and base.
  1. Thread the collar assembly all the way onto the stud of the flange saddle, then assemble the completed support including the cut pipe section and position under the flange.
Turn collar counter-clockwise to tighten.
  1. Turn the collar assembly counter-clockwise until the saddle rests snuggly under the flange connection, and in between the seismic tabs. Insure that base assembly is positioned directly under piping system. Base may be secured to the floor with ½" wedge anchors if required.